Copper Busbars

0
Technical Characteristics: 

Copper used in Maskal bus bars is CDA 110 (BS 2874 C102) standard which means it contains minimum of 99.9% pure Copper. Excellent corrosion resistance due to purity of copper is an advantage when used as an electrical conducting material. The copper bus bars are tin plated to a thickness of around 10 microns, which increases efficiency of joints and delaysoxidation of bus bars in hostile environments and high temperatures

Legend: 

I = 7.73 X A0.5 x p0.39
I = Current Rating in Amp
A = Cross Sectional Area in mm2
P = Perimeter in mm

Operations

Busbars

Description:

Rectangular with Radius Corners
Condition : Half Hard
Length : 4 metres
Purity of Copper: 99.9%



Description:

Rectangular with Radius Corners
Condition : Half Hard
Length : 4 metres
Purity of Copper: 99.9%



Size (width x thickness) mm Kilogram / meter Wt / 4 meter Current Rating (AMP) Model No.
10 X 5 0.44 1.76 206 OCCB01005
12 x 5 OCCB01205
15 X 5 0.67 2.68 282 OCCB01505
20 X 5 0.89 3.56 355 OCCB02005
25 X 5 1.11 4.44 427 OCCB02505
30 X 5 1.33 5.32 496 OCCB03005
20 X 10 1.78 7.12 540 OCCB02010
30 X 10 2.67 10.68 740 OCCB03010
40 X 10 3.56 14.24 932 OCCB04010
50 X 10 4.45 17.8 1118 OCCB05010
60 X 10 5.33 21.32 1300 OCCB06010
80 X 10 7.11 28.44 1657 OCCB08010
100 X 10 8.89 35.56 2000 OCCB10010
120 X 10 OCCB12010
150 X 10 OCCB15010